Thies Clima Sensor D: 4.9110.00.061
• Serves for measurement of environmental parameters
• With internal DCF77 receiver, transmitter located at Frankfurt/M, to synchronize the internal clock and integrate it into the data telegram
• Fields of application such as building control systems, control technology, greenhouse technology, etc.
Measuring parameters for model Nr. 4.9110.00.061:
Wind speed:
• Measurement range: 1 ... 40m/s
• Accuracy: ±0.5 m/s or ± 5% resp. of measuring value
• Electrical analogue output: 0...10 V
Air temperature:
• Measurement range: -20 ... +60°C
• Measuring element: Pt100
• Accuracy: ±0.5K at wind speed > 2.5 m/s
• Electrical analogue output: 0...10 V
Air relative humidity:
• Measurement range: 0 ... 100 %RH
• Accuracy: ±3 % at 10 ... 90 %RH at wind speed > 2.5m/s
• Electrical analogue output: 0...10 V
Brightness:
• Measurement range: 0 ... 150 kLux
• Accuracy: ±3% of measuring range
• Spectral range: 700 ... 150nm
• Electrical analogue output: 3 x 0...10 V
Twilight:
• Measurement range: 0 ... 250 Lux
• Accuracy: ±5% of measuring range
• Spectral range: 700 ... 150nm
• Electrical analogue output: 0...10 V
Precipitation:
• Precipitation: yes/no
• Sensitivity: 0.25 mm/h
• Switch-off delay: approx. 2 min.
• Electrical analogue output: 0 V = precipitation "active" or 10 V = no precipitation "passive"
• Operating voltage: 16 ... 28 VDC or 16 ... 24 VAC, approx. 250mA consumption with condensation protection
• Approx. 250mA consumption with condensation protection
• Operating temperature range: -40 ... +60°C
• Data output digital: RS485 / RS422, 1200 ... 19200 Baud, 8N1, full-duplex / half-duplex
• Data output analogue: 0 ... 10V, load resistance
• Mounting e.g. Niro-mounting brack on mast or wall
Data sheet